13  Directory of the Parameters in Installer Mode and Expert Mode

SMA Solar Technology AG

120

SI30M-44M-60H-80H-BE-en-30

Operating Manual

250.06 ComBaud

Baud rate in Bd
This value cannot be

changed with

Speedwire.

1,200

Default value for RS485

communication.

✓ ✓ ‒

4,800

9,600

19,200

115k

Default value for

Speedwire

communication.

250.09 ComAdr

Communication

address (cannot be

adjusted)

0 to 65,535 ‒

✓ ✓ 1

250.11 AfraEna

Automatic frequency

synchronization (AFRA)

(expert mode)

Disable

Disable

✖ ✓ ‒

Enable

Enable

250.23 Box

Type of

Multicluster Box used

None

None

✖ ✓ ‒

MC-Box-6

Multicluster Box 6.3

MC-Box-9

Multicluster Box 9.3

MC-Box-12

Multicluster Box 12.3

MC-Box-36

Multicluster Box 36.3

250.24 ClstMod

Cluster type (adjustable

in QCG)

SingleClst

Single cluster

✓ ✓ ‒

MainClst

Main cluster

ExtnClst

Extension cluster

250.28 ChrgCtlOp

Types of energy

sources in the system

(expert mode)

Auto

AC sources and DC

charge controllers

✖ ✓ Auto

NoFrq

DC charge controllers

only
The DC charge

controllers are not

Sunny Island Charger

devices and there are no

AC sources in the system.

SMA

Sunny Island Charger

devices only
No AC sources in the

system.

250.30 RnMod

Run Mode
Behavior under fault

conditions

RunAlways

In the event of a slave

device error, the cluster

remains in operation

✓ ✓ RunAlwa

ys

StopAlways

In the event of a device

error, the cluster stops

operation

No.

Name

Description

Value

Explanation

Default

value

This manual is related to the following products: