13 Directory of the Parameters in Installer Mode and Expert Mode
SMA Solar Technology AG
100
SI30M-44M-60H-80H-BE-en-30
Operating Manual
163# State
No.
Name
Description
Value
Explanation
163.01 BatMntStt
Status of the full charge or
equalization charge
If full charge or
equalization charge with
PV energy has not ended
after 24 hours,
163.01 BatMntStt
automatically switches to
On.
On
Full charge or equalization
charge active, energy is
drawn from the utility grid
✓ ✖
Wait
If sufficient PV energy is
available, full charge or
equalization charge active
Off
No full charge or
equalization charge active
163.02 SlfCsmpSOCArea
Current range of the state
of charge of the battery
In systems for increased
self-consumption and in
battery backup systems,
this parameter shows the
range in which the state of
charge of the battery
currently is.
PeakShaveSOC Range for prevention of
derating losses
✓ ✖
SlfCsmpSOC
Range for increased
self-consumption
PVResSOC
Range for maintaining the
state of charge of the
battery
BUResSOC
Range for the battery
backup system function
BatResSOC
Range for protection
against deep discharge
ProtResSOC
Range for protection in the
event of deep discharge
163.03 SlfCsmpSOCLim
Threshold of the current
day of the state of charge
of the battery for increased
self-consumption in %
(expert mode)
The battery can be used for
increased self-consumption
up to the displayed
threshold.
5% to 90%
‒
✓ ✖