3 generator or utility grid category (3xx) – SMA SI 3.0-11 User Manual

Page 51

background image

SMA Solar Technology AG

9  Troubleshooting

Operating Manual

SI30M-44M-60H-80H-BE-en-30

51

9.4.3 Generator or Utility Grid Category (3xx)

No.

Name

Level Cause

Corrective measures

W 309 RlyProtect

1

Excessive current has been

applied to the internal

transfer relay of the master.

• Reduce the total power of the loads, e.g.,

by staggering their use over time.

Connect the loads with very high power

directly to the generator whenever

possible or connect the utility grid. Ensure

that the generator is not overloaded.

In off-grid systems, ensure that the country

data sets of the SMA inverters are set to

stand-alone grid operation

(see the installation manuals of the SMA

inverters).

W 310 RlyProtectSlv1

1

Excessive current has been

applied to the internal

transfer relay of slave 1.

W 311 RlyProtectSlv2

1

Excessive current has been

applied to the internal

transfer relay of slave 2.

F 314 ExtVtgLoss

2

The voltage and/or

frequency of the generator

or the utility grid are outside

the configured range.

Corrective measures for a generator:

Adjust the thresholds for generator

frequency and/or voltage on the

Sunny Island (see the Sunny Island

inverter installation manual). Observe

and analyze the measured values

134.02 ExtVtg and 134.04 ExtFrq

during operation.

Adjust the generator voltage and/or

generator frequency.

Corrective measures in battery backup

systems:

• Contact the SMA Service Line, if required.