9.4.2 Battery Category (2xx)
F 169 Overload30min
3
The 30 minute overload capacity
of the master has been exceeded.
• Reduce the power of the loads.
W 170 Overload30minSlv1
1
The 30 minute overload capacity
of slave 1 has been exceeded.
W 171 Overload30minSlv2
1
The 30 minute overload capacity
of slave 2 has been exceeded.
F 172 Overload
3
The overload capacity of the
master has been exceeded.
W 173 OverloadSlv1
1
The overload capacity of slave 1
has been exceeded.
W 174 OverloadSlv2
1
The overload capacity of slave 2
has been exceeded.
F 175 StopSlvError
1
A slave has disconnected
• Contact the SMA Service Line.
F 176 CurTrfSns
4
Internal current sensor is not
functioning correctly.
No.
Name
Level Cause
Corrective measures
F 201 VBATMAX
2
Battery voltage at the master is
above the permissible
measurement range.
• Check whether the value of the
parameter 120.02 BatVtg is above
65.0 V. If the value is above 65.0 V,
check the settings of the DC sources and
ensure that the battery capacity is
sufficient. When doing so, bear in mind
the technical data for the battery at the
DC connection (see the Sunny Island
inverter installation manual).
•
Ensure that the DC sources are correctly
connected and configured.
W 202 VBATMAXSL1
1
Battery voltage at slave 1 is
above the permissible
measurement range.
W 203 VBATMAXSL2
1
Battery voltage at slave 2 is
above the permissible
measurement range.
F 206 BatTmpHi
3
The battery temperature is too
high.
• Wait for the battery to cool down.
Tip: Protect the battery against
temperatures above 25°C. This helps
prevent premature aging of the battery.
•
Check whether the electrical resistance of
the battery temperature sensor is approx.
2,000 Ω at 20°C to 25°C. If the
resistance deviates strongly from this
value, replace the sensor.
No.
Name
Level Cause
Corrective measures