9  Troubleshooting

SMA Solar Technology AG

54

SI30M-44M-60H-80H-BE-en-30

Operating Manual

W 343 AcVtglim

1

The master disconnects from

the external energy source

because the voltage at

connection AC2 is too high

or the battery voltage too

low.

• Contact the SMA Service Line if required.

W 344 AcVtglimSlv1

1

Slave 1 disconnects from the

external energy source

because the voltage at

connection AC2 is too high

or the battery voltage too

low.

W 345 AcVtglimSlv2

1

Slave 2 disconnects from the

external energy source

because the voltage at

connection AC2 is too high

or the battery voltage too

low.

W 347 ExtOverload

1

The master disconnects from

the utility grid due to line

conductor failure/overload

at connection AC2.

• Reduce the total power of the loads, e.g.,

by staggering their use over time.

Ensure that there is not a short circuit

present at connection AC2.

W 348 ExtOverloadSlv1

1

Slave 1 disconnects from the

utility grid due to line

conductor failure/overload

at connection AC2.

W 349 ExtOverloadSlv2

1

Slave 2 disconnects from the

utility grid due to line

conductor failure/overload

at connection AC2.

W 351 ExtScirDet

1

There is a short circuit

present at connection AC2

of the master.

Eliminate the short circuit.

W 352 ExtScirDetSlv1

1

There is a short circuit

present at connection AC2

of slave 1.

W 353 ExtScirDetSlv2

1

There is a short circuit

present at connection AC2

of slave 2.

W 355 PhsAngErr

1

Assignment of the line

conductors of the external

energy source to the AC2

connections of the

Sunny Island does not result

in a right-rotating magnetic

field.

Ensure that the master is connected to L1,

slave 1 to L2, and slave 2 to L3.

No.

Name

Level Cause

Corrective measures