SMA SI 3.0-11 User Manual
Page 112

13 Directory of the Parameters in Installer Mode and Expert Mode
SMA Solar Technology AG
112
SI30M-44M-60H-80H-BE-en-30
Operating Manual
234.11 GnErrStpTm
Stop time of the
generator in the event of
an error in hours
(expert mode)
0 h to 24 h
‒
✖ ✓ 1 h
234.12 GnWarmTm
Warm-up time in seconds 5 s to 900 s
‒
✖ ✓ 60 s
234.13 GnRvPwr
Active power of the
generator reverse power
in W (expert mode)
0 W to 5,000 W
One Sunny Island
or single-cluster
system
✖ ✓ 100 W
0 W to 20,000 W
Multicluster
system
100 W
234.14 GnRvTm
Permissible time for
reverse power or reverse
current, in s
(expert mode)
0 s to 900 s
‒
✖ ✓ 30 s
234.15 GnCtlMod
Generator control
(expert mode)
The generator control
limits the consumption of
generator current.
Cur
Fixed threshold for
current limitation
✖ ✓ Cur
CurFrq
Frequency-depen
dent current
limitation
234.20 GnAlSns
Anti-islanding sensitivity
(expert mode)
Low
Low
✖ ✓ Normal
Medium
Medium
Normal
Normal
High
High
234.41 GnCurCtlMod Enable I-Loop in
generator operation
(expert mode, only with
SI6.0H-11 and
SI8.0H-11)
I-Loop enables
generators with
inadequate voltage
regulation to be used in
the system.
Droop
Standard
generator
operation without
I-Loop
✖ ✓ Droop
CurCtl
Current-controlled
generator
operation with
I-Loop
234.42 GnAIFac
Anti-islanding factor in
current-controlled
generator operation with
I-Loop (expert mode)
0.00 to 1.00
−
✖ ✓ 0.10
No.
Name
Description
Value
Explanation
Default
value