9  Troubleshooting

Operating Manual

SI30M-44M-60H-80H-BE-en-30

41

9 Troubleshooting

9.1 Sunny Island Inverter Behavior Under Fault Conditions

Display of errors, warnings, and events

Pending warnings and errors are shown automatically on the display of the Sunny Remote Control until the cause of the

warning or error is no longer logged by the Sunny Island or has been acknowledged. Events are logged by the

Sunny Island. The following menus log warnings, errors and events:

• 410# Error active - display of currently pending warnings and errors
• 420# Error history - warning and error history
• 430# Event history - events history
• In systems for increased self-consumption and battery backup systems: 440# Error Grid - history of the last five utility

grid errors

Structure of display numbers

Each error and each event has a unique three-digit display number that is determined based on the parameter or

measurement value assignment. Events and errors use the same number range:

• 1xx - Sunny Island
• 2xx - Battery
• 3xx - Generator or utility grid
• 4xx - Generator
• 5xx - Utility grid
• 6xx - Relay
• 7xx - System
• 8xx - External devices and components
• 9xx - General

Error Levels

The Sunny Island distinguishes between five different levels of errors, each requiring different user interaction.

Meaning of abbreviations
F
indicates an error, W a warning, and E an event.
In the event of an error, the display shows whether the error has come or gone using ! for "Set" and C for "Clear".

Level

Designation

Display on the

Sunny Remote

Control

Explanation

1

Warning

Warning

Warning, the Sunny Island continues to run. Information in standard

mode indicating that a warning has been generated.

2

Malfunction 1 Malfunction

Malfunction that is only detectable during operation. The Sunny Island

shuts down. Restart can be initiated immediately (e.g., via autostart).

3

Malfunction 2 Malfunction

Malfunction that is also detectable in standby mode. The Sunny Island

shuts down. Restart is blocked until the malfunction is no longer detected

by the Sunny Island.