SMA SI 3.0-11 User Manual
Page 108

13 Directory of the Parameters in Installer Mode and Expert Mode
SMA Solar Technology AG
108
SI30M-44M-60H-80H-BE-en-30
Operating Manual
232.44 P-WGra
Increase of the active
power limitation in
%
/
Hz
(expert mode, protected
by SMA Grid Guard)
10
%
⁄
Hz
to
130
%
⁄
Hz
‒
✓ ✓ 40
%
⁄
Hz
232.46 WGraRecon
Power gradient following
grid error in % (expert
mode, protected by
SMA Grid Guard)
1% to 100%
‒
✓ ✓ 10%
232.48 Q-VArMod
Setpoint of the
displacement power
factor cos φ
(expert mode, protected
by SMA Grid Guard)
Off
Disable
✓ ✓ −
PFCnst
Constant
displacement
power factor
cos φ
PFCtlW
Automatic
adaptation of the
displacement
power factor
according to the
current active
power
232.49 PF-PF
Setpoint of the
displacement power
factor cos φ at PFCnst
(expert mode, protected
by SMA Grid Guard)
0.8 to 1
Code of Practice
VDE-AR-N 4105
✓ ✓ 0.9
Standard
AS-4777
1
232.50 PF-PFExt
Type of excitation of the
displacement power
factor cos φ at PFCnst
(expert mode, protected
by SMA Grid Guard)
OvExt
Lagging
✓ ✓ UnExt
UnExt
Leading
232.51 PF-PFStr
Displacement power
factor cos φ at the start
point at PFCtlW (expert
mode, protected by
SMA Grid Guard)
0.8 to 1
‒
✓ ✓ 1
232.52 PF-PFExtStr
Excitation type at the start
point at PFCtlW (expert
mode, protected by
SMA Grid Guard)
OvExt
Lagging
✓ ✓ OvExt
UnExt
Leading
232.53 PF-WNomStr
Proportion of the
maximum active power
at the start point in % at
PFCtlW (expert mode,
protected by
SMA Grid Guard)
0% to 232.56
PF-WNomStop
‒
✓ ✓ 50%
No.
Name
Description
Value
Explanation
Default
value