beautypg.com

7 authent (270#) – SMA SI 3.0-11 User Manual

Page 122

background image

13  Directory of the Parameters in Installer Mode and Expert Mode

SMA Solar Technology AG

122

SI30M-44M-60H-80H-BE-en-30

Operating Manual

262# BatUsage

13.2.7 Authent (270#)

No.

Name

Description

Value

(plain text

no.)

Explanation

Default

value

262.01 ProtResSOC

Range for protection in

the event of deep

discharge as a

percentage of the battery

capacity (expert mode)

10% to 20% Lead-acid batteries

✓ ✖ 10%

3% to 20%

Lithium-ion batteries

✓ ✖ 3%

262.02 BatResSOC

Range for protection

against deep discharge

as a percentage of the

battery capacity

(expert mode)

2% to 50%

Lithium-ion battery,

self-consumption only

✓ ✖ 2%

Lithium-ion battery,

battery backup

system

✓ ✖ 10%

Lead-acid battery,

self-consumption only

✓ ✖ 30%

Lead-acid battery,

battery backup

system

✓ ✖ 5%

262.03 BUResSOC

Range for the battery

backup function on the

longest day of the year

as a percentage of the

battery capacity

(expert mode)

0% to 100% ‒

✓ ✖ 0%

262.04 PVResSOC

Range for maintaining

the state of charge of the

battery as a percentage

of the nominal capacity

(expert mode)

4% to 20%

✓ ✖ 5%

262.05 MinSlfCsmpSOC

Range for increased

self-consumption on the

shortest day of the year

as a percentage of the

battery capacity

(expert mode)

0% to 100% Lithium-ion battery

✓ ✖ 70%

Lead-acid battery

✓ ✖ 35%

No.

Name

Description

270.01 Auth.Code

Entry of the SMA Grid Guard code

✓ ✖

This manual is related to the following products: