13 Directory of the Parameters in Installer Mode and Expert Mode
SMA Solar Technology AG
122
SI30M-44M-60H-80H-BE-en-30
Operating Manual
262# BatUsage
13.2.7 Authent (270#)
No.
Name
Description
Value
(plain text
no.)
Explanation
Default
value
262.01 ProtResSOC
Range for protection in
the event of deep
discharge as a
percentage of the battery
capacity (expert mode)
10% to 20% Lead-acid batteries
✓ ✖ 10%
3% to 20%
Lithium-ion batteries
✓ ✖ 3%
262.02 BatResSOC
Range for protection
against deep discharge
as a percentage of the
battery capacity
(expert mode)
2% to 50%
Lithium-ion battery,
self-consumption only
✓ ✖ 2%
Lithium-ion battery,
battery backup
system
✓ ✖ 10%
Lead-acid battery,
self-consumption only
✓ ✖ 30%
Lead-acid battery,
battery backup
system
✓ ✖ 5%
262.03 BUResSOC
Range for the battery
backup function on the
longest day of the year
as a percentage of the
battery capacity
(expert mode)
0% to 100% ‒
✓ ✖ 0%
262.04 PVResSOC
Range for maintaining
the state of charge of the
battery as a percentage
of the nominal capacity
(expert mode)
4% to 20%
‒
✓ ✖ 5%
262.05 MinSlfCsmpSOC
Range for increased
self-consumption on the
shortest day of the year
as a percentage of the
battery capacity
(expert mode)
0% to 100% Lithium-ion battery
✓ ✖ 70%
Lead-acid battery
✓ ✖ 35%
No.
Name
Description
270.01 Auth.Code
Entry of the SMA Grid Guard code
✓ ✖