9 Troubleshooting
SMA Solar Technology AG
52
SI30M-44M-60H-80H-BE-en-30
Operating Manual
W 315 ExtVtgLo
1
The voltage of the generator
or the utility grid at the
master is too low.
Corrective measures for a generator:
•
Adjust the thresholds for generator
voltage on the Sunny Island
(see the Sunny Island inverter installation
manual). Observe and analyze the
measured values 134.02 ExtVtg during
operation.
•
If possible, adjust the generator voltage.
Corrective measures in battery backup
systems:
• Contact the SMA Service Line, if required.
W 316 ExtVtgLoSlv1
1
The voltage of the generator
or the utility grid at slave 1 is
too low.
W 317 ExtVtgLoSlv2
1
The voltage of the generator
or the utility grid at slave 2 is
too low.
W 319 ExtVtgHi
1
The voltage of the generator
or the utility grid at the
master is too high.
W 320 ExtVtgHiSlv1
1
The voltage of the generator
or the utility grid at slave 1 is
too high.
W 321 ExtVtgHiSlv2
1
The voltage of the generator
or the utility grid at slave 2 is
too high.
W 323 ExtFrqLo
1
The frequency of the
generator or the utility grid at
the master is too low.
Corrective measures for a generator:
• The generator may be overloaded.
Reduce the total power of the loads by
staggering their use over time.
•
Adjust the thresholds for generator
frequency on the Sunny Island (see the
Sunny Island inverter installation
manual). Observe and analyze the
measured values 134.04 ExtFrq during
operation.
•
Adjust the frequency of the external
energy source.
Corrective measures for a utility grid:
• Contact the SMA Service Line, if required.
W 324 ExtFrqLoSlv1
1
The frequency of the
generator or the utility grid at
slave 1 is too low.
W 325 ExtFrqLoSlv2
1
The frequency of the
generator or the utility grid at
slave 2 is too low.
W 327 ExtFrqHi
1
The frequency of the
generator or the utility grid at
the master is too high.
W 328 ExtFrqHiSlv1
1
The frequency of the
generator or the utility grid at
slave 1 is too high.
W 329 ExtFrqHiSlv2
1
The frequency of the
generator or the utility grid at
slave 2 is too high.
No.
Name
Level Cause
Corrective measures