9  Troubleshooting

SMA Solar Technology AG

52

SI30M-44M-60H-80H-BE-en-30

Operating Manual

W 315 ExtVtgLo

1

The voltage of the generator

or the utility grid at the

master is too low.

Corrective measures for a generator:

Adjust the thresholds for generator

voltage on the Sunny Island

(see the Sunny Island inverter installation

manual). Observe and analyze the

measured values 134.02 ExtVtg during

operation.

If possible, adjust the generator voltage.

Corrective measures in battery backup

systems:

• Contact the SMA Service Line, if required.

W 316 ExtVtgLoSlv1

1

The voltage of the generator

or the utility grid at slave 1 is

too low.

W 317 ExtVtgLoSlv2

1

The voltage of the generator

or the utility grid at slave 2 is

too low.

W 319 ExtVtgHi

1

The voltage of the generator

or the utility grid at the

master is too high.

W 320 ExtVtgHiSlv1

1

The voltage of the generator

or the utility grid at slave 1 is

too high.

W 321 ExtVtgHiSlv2

1

The voltage of the generator

or the utility grid at slave 2 is

too high.

W 323 ExtFrqLo

1

The frequency of the

generator or the utility grid at

the master is too low.

Corrective measures for a generator:

• The generator may be overloaded.

Reduce the total power of the loads by

staggering their use over time.

Adjust the thresholds for generator

frequency on the Sunny Island (see the

Sunny Island inverter installation

manual). Observe and analyze the

measured values 134.04 ExtFrq during

operation.

Adjust the frequency of the external

energy source.

Corrective measures for a utility grid:

• Contact the SMA Service Line, if required.

W 324 ExtFrqLoSlv1

1

The frequency of the

generator or the utility grid at

slave 1 is too low.

W 325 ExtFrqLoSlv2

1

The frequency of the

generator or the utility grid at

slave 2 is too low.

W 327 ExtFrqHi

1

The frequency of the

generator or the utility grid at

the master is too high.

W 328 ExtFrqHiSlv1

1

The frequency of the

generator or the utility grid at

slave 1 is too high.

W 329 ExtFrqHiSlv2

1

The frequency of the

generator or the utility grid at

slave 2 is too high.

No.

Name

Level Cause

Corrective measures