beautypg.com

SMA SI 3.0-11 User Manual

Page 107

background image

SMA Solar Technology AG

13  Directory of the Parameters in Installer Mode and Expert Mode

Operating Manual

SI30M-44M-60H-80H-BE-en-30

107

232.14 GdVtgMinDel

Lower frequency

difference for valid grid

connection in Hz
(expert mode, protected

by SMA Grid Guard)

0.00 Hz to

2.50 Hz

✓ ✓ 0.02 Hz

232.15 GdFrqMaxDel Upper frequency

difference for valid grid

connection in Hz
(expert mode, protected

by SMA Grid Guard)

0.00 Hz to

2.50 Hz

VDE_AR_4105

✓ ✓ 1.45 Hz

0.00 Hz to

0.20 Hz

230 V/50 Hz

0.02 Hz

0.00 Hz to

0.20 Hz

220 V/60 Hz

0.02 Hz

232.16 GdAlSns

Sensitivity of the

anti-islanding detection

(expert mode, protected

by SMA Grid Guard)

Low

Low

✓ ✓ Normal

Medium

Medium

Normal

Normal

High

High

232.40 GdRtCurSrc

Place of reactive current

compensation in grid

operation (expert mode)

External

Sunny Island

compensates all

reactive currents.

✓ ✖ External

Inverter

Sunny Island does

not compensate

reactive currents.

Shared

Sunny Island

partially

compensates

reactive currents.

232.41 P-WCtlHzMod Frequency-dependent

active power limitation

(expert mode, protected

by SMA Grid Guard)

Off

Disable

✓ ✓ −

WCtlHz

Enable

232.42 P-HzStr

Start frequency of the

active power limitation in

Hz (protected by

SMA Grid Guard)

0.0 Hz to 5.0 Hz This value defines

how many Hz

above

210.02 InvFrqN

om the active

power limitation

starts.

✓ ✖ 0.2 Hz

232.43 P-HzStop

End frequency of the

active power limitation in

Hz (protected by

SMA Grid Guard)

0.0 Hz to 5.0 Hz This values defines

how many Hz

above

210.02 InvFrqN

om the active

power limitation

stops.

✓ ✖ 0.2 Hz

No.

Name

Description

Value

Explanation

Default

value

This manual is related to the following products: