SMA SI 3.0-11 User Manual
Page 107
SMA Solar Technology AG
13 Directory of the Parameters in Installer Mode and Expert Mode
Operating Manual
SI30M-44M-60H-80H-BE-en-30
107
232.14 GdVtgMinDel
Lower frequency
difference for valid grid
connection in Hz
(expert mode, protected
by SMA Grid Guard)
0.00 Hz to
2.50 Hz
−
✓ ✓ 0.02 Hz
232.15 GdFrqMaxDel Upper frequency
difference for valid grid
connection in Hz
(expert mode, protected
by SMA Grid Guard)
0.00 Hz to
2.50 Hz
VDE_AR_4105
✓ ✓ 1.45 Hz
0.00 Hz to
0.20 Hz
230 V/50 Hz
0.02 Hz
0.00 Hz to
0.20 Hz
220 V/60 Hz
0.02 Hz
232.16 GdAlSns
Sensitivity of the
anti-islanding detection
(expert mode, protected
by SMA Grid Guard)
Low
Low
✓ ✓ Normal
Medium
Medium
Normal
Normal
High
High
232.40 GdRtCurSrc
Place of reactive current
compensation in grid
operation (expert mode)
External
Sunny Island
compensates all
reactive currents.
✓ ✖ External
Inverter
Sunny Island does
not compensate
reactive currents.
Shared
Sunny Island
partially
compensates
reactive currents.
232.41 P-WCtlHzMod Frequency-dependent
active power limitation
(expert mode, protected
by SMA Grid Guard)
Off
Disable
✓ ✓ −
WCtlHz
Enable
232.42 P-HzStr
Start frequency of the
active power limitation in
Hz (protected by
SMA Grid Guard)
0.0 Hz to 5.0 Hz This value defines
how many Hz
above
210.02 InvFrqN
om the active
power limitation
starts.
✓ ✖ 0.2 Hz
232.43 P-HzStop
End frequency of the
active power limitation in
Hz (protected by
SMA Grid Guard)
0.0 Hz to 5.0 Hz This values defines
how many Hz
above
210.02 InvFrqN
om the active
power limitation
stops.
✓ ✖ 0.2 Hz
No.
Name
Description
Value
Explanation
Default