13 Directory of the Parameters in Installer Mode and Expert Mode
Operating Manual
SI30M-44M-60H-80H-BE-en-30
115
13.2.4 Relay (240#)
241# General
No.
Name
Description
Value
Explanation
Default
value
241.01 Rly1Op Multifunction
relay 1 function
Off
The multifunction relay is always in
non-operative mode.
✓ ✓ AutoGn
On
The multifunction relay is permanently
activated.
AutoGn
The Sunny Island automatically
requests the generator. In case of a
generator request, the multifunction
relay is activated.
AutoLodExt
1-level load shedding
When connecting the generator, the
Sunny Island stops the load
shedding. When the loads are to be
shed, the multifunction relay is
deactivated.
AutoLod1Soc
1-level load shedding or first level of
2-level load shedding
When the upper SOC threshold is
reached, the Sunny Island ends load
shedding. When the loads are to be
shed, the multifunction relay is
deactivated.
AutoLod2Soc
Second level of 2-level load shedding
When the upper SOC threshold is
reached, the Sunny Island ends load
shedding. When the loads are to be
shed, the multifunction relay is
deactivated.
Tm1
Timer 1
The Sunny Island controls external
processes time-dependently. When
the set time #243 Timer is reached,
the multifunction relay is activated.
Tm2
Timer 2
The Sunny Island controls external
processes time-dependently. When
the set time #243 Timer is reached,
the multifunction relay is activated.