13  Directory of the Parameters in Installer Mode and Expert Mode

Operating Manual

SI30M-44M-60H-80H-BE-en-30

115

13.2.4 Relay (240#)

241# General

No.

Name

Description

Value

Explanation

Default

value

241.01 Rly1Op Multifunction

relay 1 function

Off

The multifunction relay is always in

non-operative mode.

✓ ✓ AutoGn

On

The multifunction relay is permanently

activated.

AutoGn

The Sunny Island automatically

requests the generator. In case of a

generator request, the multifunction

relay is activated.

AutoLodExt

1-level load shedding
When connecting the generator, the

Sunny Island stops the load

shedding. When the loads are to be

shed, the multifunction relay is

deactivated.

AutoLod1Soc

1-level load shedding or first level of

2-level load shedding
When the upper SOC threshold is

reached, the Sunny Island ends load

shedding. When the loads are to be

shed, the multifunction relay is

deactivated.

AutoLod2Soc

Second level of 2-level load shedding
When the upper SOC threshold is

reached, the Sunny Island ends load

shedding. When the loads are to be

shed, the multifunction relay is

deactivated.

Tm1

Timer 1
The Sunny Island controls external

processes time-dependently. When

the set time #243 Timer is reached,

the multifunction relay is activated.

Tm2

Timer 2
The Sunny Island controls external

processes time-dependently. When

the set time #243 Timer is reached,

the multifunction relay is activated.