F 141 InvVtgLo

2

The voltage at connection AC1 of

the master is too low due to AC

sources in the system.

Ensure that the Sunny Island is

functional. For this, disconnect all

AC sources and loads from the

Sunny Island and restart the

Sunny Island.

Find the cause of the undervoltage

through measurement and

step-by-step connection of the AC

sources and loads.

W 142 InvVtgLoSlv1

1

The voltage at connection AC1 of

slave 1 is too low due to AC

sources in the system.

W 143 InvVtgLoSlv2

1

The voltage at connection AC1 of

slave 2 is too low due to AC

sources in the system.

F 158 VtgOnAC1Det

2

The master has measured an

undesired voltage at connection

AC1.

A bypass switch may have bridged the

internal transfer relay.

• Ensure that the bypass switch is in

the position for operation with the

Sunny Island.

Ensure that the Sunny Island is

functional. For this, disconnect all

AC sources and loads from the

Sunny Island and restart the

Sunny Island.

A voltage source (e.g., generator) may

have been connected to the

connection AC1.

Disconnect voltage source from

connection AC1 and connect to

connection AC2 (see the

Sunny Island inverter installation

manual).

W 159 VtgOnAC1DetSlv1

1

Slave 1 has measured an

undesired voltage at connection

AC1.

W 160 VtgOnAC1DetSlv2

1

Slave 2 has measured an

undesired voltage at connection

AC1.

F 162 OvrCurDet

2

Too much current is flowing

through the DC connection of the

master.

• Reduce the power of the loads.

W 163 OvrCurDetSlv1

1

Too much current is flowing

through the DC connection of

slave 1.

W 164 OvrCurDetSlv2

1

Too much current is flowing

through the DC connection of

slave 2.

F 166 Overload5min

3

The five minute overload capacity

of the master has been exceeded.

W 167 Overload5minSlv1

1

The five minute overload capacity

of slave 1 has been exceeded.

W 168 Overload5minSlv2

1

The five minute overload capacity

of slave 2 has been exceeded.