beautypg.com

SMA SI 3.0-11 User Manual

Page 116

background image

13  Directory of the Parameters in Installer Mode and Expert Mode

SMA Solar Technology AG

116

SI30M-44M-60H-80H-BE-en-30

Operating Manual

241.01 Rly1Op Multifunction

relay 1 function

(continued)

ExtPwrDer

The Sunny Island controls additional

loads in order to put excess energy to

practical use. When excessive energy

can be used, the multifunction relay is

activated.

✓ ✓ AutoGn

GnRn

When the generator is running and

connected, the multifunction relay is

activated.

ExtVfOk

When the voltage and frequency of

the external energy source are within

the valid range for the connection, the

multifunction relay is activated.

GdOn

When the utility grid is connected, the

multifunction relay is activated.

Error

When an error message is pending,

the multifunction relay is deactivated.

Warn

When a warning is pending, the

multifunction relay is activated.

Run

When the Sunny Island or the cluster

is in operation, the multifunction relay

is activated.

BatFan

The Sunny Island controls the battery

room fan. When the battery room is

to be ventilated, the multifunction

relay is activated.

AcdCir

The Sunny Island controls the

electrolyte pump of the battery. When

the electrolyte is to be circulated, the

multifunction relay is activated.

MccBatFan

The Sunny Island controls the battery

room fan for all clusters together.

When the battery room is to be

ventilated, the multifunction relay is

activated.

MccAutoLod

1-level load shedding
When all batteries have reached the

upper SOC threshold, the

Sunny Island ends load shedding.

When the loads are to be shed, the

multifunction relay is deactivated.

CHPReq

No function

CHPAdd

No function

No.

Name

Description

Value

Explanation

Default