9  Troubleshooting

SMA Solar Technology AG

60

SI30M-44M-60H-80H-BE-en-30

Operating Manual

F 743 CANCom

3

Internal device CAN communication

of the master is disturbed.

Ensure that the terminators in the

communication bus are attached.

Ensure that undamaged CAT5e

cables are used for communication

and that the cables are plugged in

correctly.

• Contact the SMA Service Line.

W 744 CANComSlv1

1

Internal device CAN communication

of slave 1 is disturbed.

W 745 CANComSlv2

1

Internal device CAN communication

of slave 2 is disturbed.

W 747 InvTmpSnsSlv1

1

Temperature sensor on the

transformer of slave 1 is defective.

• Contact the SMA Service Line.

W 748 InvTmpSnsSlv2

1

Temperature sensor on the

transformer of slave 2 is defective.

W 750 InvTmpSnsSlv1

1

Temperature sensor on the heat sink

of slave 1 is defective.

W 751 InvTmpSnsSlv2

1

Temperature sensor on the heat sink

of slave 2 is defective.

W 753 DateInvalid

1

System time is invalid.

• Select the parameter 250.02 Dt

and set the date. Select the

parameter 250.03 Tm and set the

time.

F 754 BoxCom

2

Communication with Multicluster Box

is interrupted.

Ensure that undamaged CAT5e

cables are used for communication

and that the cables are plugged in

correctly.

Ensure that the communication bus

is equipped with a terminator at

both ends.

W 755 LoBatMod1

1

Battery protection mode protects the

battery. Level 1 is active.

• Disconnect the loads, start the

generator, start the Sunny Island

and charge the battery.

W 756 LoBatMod2

1

Battery protection mode protects the

battery. Level 2 is active.

W 757 LoBatMod3

1

Battery protection mode protects the

battery. Level 3 is active.

F 758 McNoVtg

2

Voltage of the main cluster cannot be

measured at the master.

• Ensure that all circuit breakers of

the Sunny Island inverters in the

Multicluster Box are closed.

Ensure that the cabling at

connection AC1 is correctly

installed.

W 759 McNoVtgSv1

1

Voltage of the main cluster cannot be

measured at slave 1.

W 760 McNoVtgSlv2

1

Voltage of the main cluster cannot be

measured at slave 2.

No.

Name

Level Cause

Corrective measures