beautypg.com

4 starting and stopping the system, 1 switching on the sunny island, 2 starting the system – SMA SI 3.0-11 User Manual

Page 18

background image

4  Starting and Stopping the System

SMA Solar Technology AG

18

SI30M-44M-60H-80H-BE-en-30

Operating Manual

4 Starting and Stopping the System

4.1 Switching on the Sunny Island

Requirements:

☐ The load-break switch in the DC cable must be closed.
☐ The Sunny Island must not have switched itself off (see Section 9.6 "Charging the Battery After Automatic Shutdown

in Off-Grid Systems", page 72).

Procedure:

• For systems with one Sunny Island, press the "On" button on the

Sunny Island.

• For systems with up to three Sunny Island inverters, press and hold

the "On" button on the master until an acoustic signal sounds.

• For multicluster systems, press and hold the "On" button on each

master until an acoustic signal sounds.

☑ The inverter LED on each Sunny Island inverter is glowing orange and the Sunny Island inverters are in standby.

4.2 Starting the System

Requirement:

☐ All Sunny Island inverters must be switched on.

Procedure:

• Press the start-stop button on the Sunny Island and hold it until an

acoustic signal sounds.

or

Press and hold the button on the Sunny Remote Control until an acoustic signal sounds.

☑ The inverter LED on each Sunny Island is glowing green.