9  Troubleshooting

Operating Manual

SI30M-44M-60H-80H-BE-en-30

63

W 815 BoxQ5

1

Contactor Q5 in the

Multicluster Box is not

functioning correctly.

• Reset the off-grid system. For this,

disconnect the off-grid system and restart.

The configuration may be incorrect.

Start the QCG and reconfigure

multicluster operation (see the

Sunny Island inverter installation manual).

• Contact the SMA Service Line.

F 816 BoxQ7

2

Contactor Q7 in the

Multicluster Box is not

functioning correctly.

F 817 BoxQ9

4

Contactor Q9 in the

Multicluster Box is not

functioning correctly.

F 818 BoxPhsFail

4

One line conductor of a

Sunny Island inverter is

missing.

• Ensure that all circuit breakers of the

Sunny Island inverters in the

Multicluster Box are closed.

• Reset the off-grid system. For this,

disconnect the off-grid system and restart.

Search for the missing line conductor and

eliminate the error. For this, with loads

connected, measure the AC voltage

between each line conductor and

between the line conductors and the

neutral conductors. If an AC voltage

deviates from the nominal voltage by

±10%, the corresponding line conductor

is missing.

W 824 BoxQ4Overload

1

Multicluster Box signals an

error at contactor Q4.

• Contact the SMA Service Line.

W 840 eHZ1ComFail

1

Faulty communication with the

feed-in meter and purchased

electricity meter

• Ensure that the optical probe is correctly

mounted.

• Ensure that the optical probe is correctly

connected.

W 841 eHZ2ComFail

1

Faulty communication with the

PV production meter

W 842 ComBoxFail

1

Faulty communication

between the Sunny Island and

the Meter Box.

Ensure that the data cables are correctly

installed.

W 843 ComBoxWD

1

The Meter Box watchdog has

triggered.

• Contact the SMA Service Line.

W 844 eHZ1ProtFail

1

Data protocol of the feed-in

and purchased electricity

meter is unknown.

W 845 eHZ2ProtFail

1

Data protocol of the PV

production meter is unknown.

W 846 eHzInFail

1

Optical probes have been

swapped.

• Swap the optical probe connections.

No.

Name

Level Cause

Corrective measures