Operating Manual
9.4.7 System Category (7xx)
No.
Name
Level Cause
Corrective measures
F 702 RsDsp
5
Signal processor has performed a
reset.
• Contact the SMA Service Line.
F 703 TimeOut
2
Time for performing a particular task
has been exceeded.
F 704 Calib
4
The system has not calibrated.
W 705 TimeOut
1
The watchdog of the signal processor
of the master has tripped.
• Contact the SMA Service Line if
required.
F 706 TimeOut
4
The watchdog of the signal processor
of the master has tripped several
times.
• Contact the SMA Service Line.
W 707 TimeOutSlv1
1
The watchdog of the signal processor
of slave 1 has tripped several times.
W 708 TimeOutSlv2
1
The watchdog of the signal processor
of slave 2 has tripped several times.
F 710 AutoStrCnt
4
Autostart meter has expired several
times in succession.
•
Read off the pending and logged
warnings and errors and eliminate
the causes.
• Ensure that the parameter 250.01
AutoStr is set to 3.
W 713 TimeOut
1
The watchdog of the operation
control unit has tripped.
• Contact the SMA Service Line if
required.
W 715 MMCUpdFail
1
The update cannot be carried out.
The type or format of the SD memory
card is not supported.
• Copy the update file to an SD
memory card with maximum 2 GB
and with FAT-16 format.
F 716 VBATMIN
2
The measured battery voltage of the
master is below the permissible
measurement range.
• Disconnect the DC loads and
charge the battery.
The usable battery capacity may be too
small, e.g., due to aging. If a load with
high power connects, the battery
voltage collapses.
•
If DC loads are installed in the
system, install load shedding for
DC loads.
•
Ensure that all battery cells are
functional.
W 717 VBATMINSL1
1
The measured battery voltage of
slave 1 is below the permissible
measurement range.
W 718 VBATMINSL2
1
The measured battery voltage of
slave 2 is below the permissible
measurement range.
F 720 InvTmpSns
4
The temperature sensor on the
transformer of the master is defective.
• Contact the SMA Service Line.
F 721 InvTmpSns
4
The temperature sensor on the heat
sink of the master is defective.