13 Directory of the Parameters in Installer Mode and Expert Mode
Operating Manual
SI30M-44M-60H-80H-BE-en-30
105
232# Grid Control
No.
Name
Description
Value
Explanation
Default
value
232.01 Country
Country data set
(protected by
SMA Grid Guard)
Other
Individual setting
✓ ✓ ‒
VDE-AR-4105
Code of Practice
VDE-AR-N 4105
−
AS4777
Standard
AS4777
232.02 GdVtgMin
Minimum line voltage
in V (expert mode,
protected by
SMA Grid Guard)
172.50 V to
210.01
InvVtgNom
230 V/50 Hz
✓ ✓ 184.00 V
220 V/60 Hz
194.00 V
232.03 GdVtgMax
Maximum line voltage
in V (expert mode,
protected by
SMA Grid Guard)
210.01
InvVtgNom to
264.50 V
230 V/50 Hz
✓ ✓ 264.50 V
220 V/60 Hz
242.00 V
232.04 GdCurNom
Nominal line current in A
(expert mode, protected
by SMA Grid Guard)
0.0 A to 50.0 A
1 inverter
SI 3.0M / 4.4M
(single-phase)
✓ ✖ 19 A
1 inverter
SI 6.0H / 8.0H
(single-phase)
✓ ✖ 26.5 A
3 inverters
SI 3.0M / 4.4M
(three-phase)
✓ ✖ 19 A
3 inverters
SI 6.0H / 8.0H
(three-phase)
✓ ✖ 34.5 A
1 inverter
SI 3.0M / 4.4M
(single-phase)
✖ ✓ 16 A
1 inverter
SI 6.0H / 8.0H
(single-phase)
✖ ✓ 16 A
0.0 A to 100.0 A 2 inverters
SI 6.0H / 8.0H
(single-phase)
✖ ✓ 16 A
0.0 A to 150.0 A 3 inverters
SI 6.0H / 8.0H
(single-phase)
✖ ✓ 16 A
0.0 A to 50.0 A
3 inverters
SI 3.0M / 4.4M
(three-phase)
✖ ✓ 16 A
3 inverters
SI 6.0H / 8.0H
(three-phase)
✖ ✓ 16 A