13  Directory of the Parameters in Installer Mode and Expert Mode

Operating Manual

SI30M-44M-60H-80H-BE-en-30

105

232# Grid Control

No.

Name

Description

Value

Explanation

Default

value

232.01 Country

Country data set

(protected by

SMA Grid Guard)

Other

Individual setting

✓ ✓ ‒

VDE-AR-4105

Code of Practice

VDE-AR-N 4105

AS4777

Standard

AS4777

232.02 GdVtgMin

Minimum line voltage

in V (expert mode,

protected by

SMA Grid Guard)

172.50 V to

210.01

InvVtgNom

230 V/50 Hz

✓ ✓ 184.00 V

220 V/60 Hz

194.00 V

232.03 GdVtgMax

Maximum line voltage

in V (expert mode,

protected by

SMA Grid Guard)

210.01

InvVtgNom to

264.50 V

230 V/50 Hz

✓ ✓ 264.50 V

220 V/60 Hz

242.00 V

232.04 GdCurNom

Nominal line current in A
(expert mode, protected

by SMA Grid Guard)

0.0 A to 50.0 A

1 inverter

SI 3.0M / 4.4M

(single-phase)

✓ ✖ 19 A

1 inverter

SI 6.0H / 8.0H

(single-phase)

✓ ✖ 26.5 A

3 inverters

SI 3.0M / 4.4M

(three-phase)

✓ ✖ 19 A

3 inverters

SI 6.0H / 8.0H

(three-phase)

✓ ✖ 34.5 A

1 inverter

SI 3.0M / 4.4M

(single-phase)

✖ ✓ 16 A

1 inverter

SI 6.0H / 8.0H

(single-phase)

✖ ✓ 16 A

0.0 A to 100.0 A 2 inverters

SI 6.0H / 8.0H

(single-phase)

✖ ✓ 16 A

0.0 A to 150.0 A 3 inverters

SI 6.0H / 8.0H

(single-phase)

✖ ✓ 16 A

0.0 A to 50.0 A

3 inverters

SI 3.0M / 4.4M

(three-phase)

✖ ✓ 16 A

3 inverters

SI 6.0H / 8.0H

(three-phase)

✖ ✓ 16 A