9  Troubleshooting

SMA Solar Technology AG

64

SI30M-44M-60H-80H-BE-en-30

Operating Manual

W 847 ComHMFaill

1

Faulty communication

between the Sunny Island and

Sunny Home Manager.

Ensure that the data cables are correctly

installed.

• Ensure that the parameter

250.06 ComBaud is set to 115k Bd.

W 851 Sic1BatShort

1

Connection of the battery to

the Sunny Island Charger 1 is

reverse poled or there is a

short circuit.

Ensure that the battery is correctly

connected to the DC connection of the

Sunny Island Charger charge controller.

Disconnect the PV array from the

Sunny Island Charger and restart the

system. This will ensure that the PV array is

not short-circuited.

W 852 Sic1BatVtgHi

1

Battery voltage at the

Sunny Island Charger 1 is too

high.

Ensure that the configuration of the

Sunny Island Charger charge controller

with the DIP switches is correct.

Ensure that all DC sources and DC loads

are correctly configured and connected.

• Reset the system. For this, switch off the

system, wait ten minutes and restart.

W 853 Sic1PvVtgHi

1

PV voltage at the Sunny Island

Charger 1 is too high.

• Contact the SMA Service Line if required.

W 854 Sic1PvVtgLo

1

No PV voltage at the

Sunny Island Charger 1 or

there is a short circuit.

W 855 Sic1TmpLo

1

Sunny Island Charger 1

reports: sensor error or device

temperature too low.

Set the Sunny Island Charger to the

operating mode "SMA operation"

(see the Sunny Island Charger charge

controller installation manual).

W 856 Sic1TmpHI

1

Sunny Island Charger 1

reports: sensor error or device

temperature too high.

Set the Sunny Island Charger to the

operating mode "SMA operation"

(see the Sunny Island Charger charge

controller installation manual).

No.

Name

Level Cause

Corrective measures