2 adjustable parameters, 1 inverter (210#), 2 battery (220#) – SMA SI 3.0-11 User Manual
Page 101: 1 inverter (210#) 13.2.2 battery (220#)

SMA Solar Technology AG
13 Directory of the Parameters in Installer Mode and Expert Mode
Operating Manual
SI30M-44M-60H-80H-BE-en-30
101
13.2 Adjustable Parameters
13.2.1 Inverter (210#)
13.2.2 Battery (220#)
221# Property
No.
Name
Description
Value
Explanation
Default
value
210.01 InvVtgNom
Nominal voltage of the
Sunny Island inverter in V
202.0 V to
253.0 V
230 V/50 Hz ✓ ✓ 230.0 V
202.0 V to
242.0 V
220 V/60 Hz
220.0 V
210.02 InvFrqNom
Nominal frequency of the
Sunny Island inverter in Hz
(expert mode)
45.0 Hz to
55.0 Hz
230 V/50 Hz ✓ ✓ 50.0 Hz
55.0 Hz to
65.0 Hz
220 V/60 Hz
60.0 Hz
210.03 InvChrgCurMax Maximum AC current during
charging and discharging in A
(expert mode)
The actual AC current can be
limited due to normative
requirements.
0 A to 26.1 A SI 8.0H
✓ ✓ 26.1 A
0 A to 20.0 A SI 6.0H
20.0 A
0 A to 14.3 A SI 4.4M
14.3 A
0 A to 10 A
SI 3.0M
10 A
/05*$&
Damage to the battery due to incorrect settings
Settings of the parameters in the menu 220# Battery influence the charging behavior of the Sunny Island. Incorrect
settings lead to premature aging of the battery.
• Ensure that the values recommended by the battery manufacturer are set (refer to the technical data of the battery
in the manufacturer documentation).
No.
Name
Description
Value
Explanation
Default
value
221.01 BatTyp
Battery type
VRLA
Valve-regulated
lead–acid battery
with immobilized
electrolyte in gel
or glass mat
✓ ✓ ‒
FLA
Valve-regulated
lead–acid battery
with liquid
electrolyte
LiIon
Lithium-ion battery