SMA SI 3.0-11 User Manual
Page 103

SMA Solar Technology AG
13 Directory of the Parameters in Installer Mode and Expert Mode
Operating Manual
SI30M-44M-60H-80H-BE-en-30
103
223# Protection
222.09 ChrgVtgEqu
Cell voltage setpoint for
equalization charge in V
(expert mode)
2.30 V to
2.70 V
Off-grid
✖ ✓ 2.45 V
VRLA, on-grid ✓ ✖ 2.55 V
FLA, on-grid
✓ ✖ 2.50 V
222.10 ChrgVtgFlo
Cell voltage setpoint for float
charge in V (expert mode)
2.20 V to
2.40 V
‒
✓ ✓ 2.25 V
222.11 BatTmpCps
Battery temperature
compensation in
mV
/
°C
(expert mode)
0.0
mV
⁄
°C
to
10.0
mV
⁄
°C
‒
✓ ✓ 4.0
mV
⁄
°C
222.12 AutoEquChrgEna Automatic equalization charge
(expert mode)
Disable
Disable
✓ ✓ Enable
Enable
Enable
222.13 BatChrgVtgMan
Manual setpoint of the battery
charging voltage with disabled
battery management in V
(expert mode)
41.0 V to
63.0 V
‒
✓ ✓ 54.0 V
No.
Name
Description
Value
Default
value
223.01 BatPro1TmStr
Start time of the battery protection mode level 1
in hh:mm:ss (expert mode)
00:00:00 to
23:59:59
✖ ✓ 22:00:00
223.02 BatPro1TmStp Stop time of the battery protection mode level 1
in hh:mm:ss (expert mode)
00:00:00 to
23:59:59
✖ ✓ 06:00:00
223.03 BatPro2TmStr
Start time of the battery protection mode level 2
in hh:mm:ss (expert mode)
00:00:00 to
23:59:59
✖ ✓ 17:00:00
223.04 BatPro2TmStp Stop time of the battery protection mode level 2
in hh:mm:ss (expert mode)
00:00:00 to
23:59:59
✖ ✓ 09:00:00
223.05 BatPro1Soc
SOC for battery protection mode level 1 in %
(expert mode)
0% to 70%
✖ ✓ 20%
223.06 BatPro2Soc
SOC for battery protection mode level 2 in %
(expert mode)
0% to 70%
✖ ✓ 15%
223.07 BatPro3Soc
SOC for battery protection mode level 3 in %
(expert mode)
0% to 70%
✖ ✓ 10%
223.08 BatProTmm
Minimum time (in minutes) during which there is
no battery current for switching to battery
protection mode (expert mode)
If the minimum time has elapsed and no battery
current was present, the Sunny Island can switch
to battery protection mode.
1 min to
20 min
✖ ✓ 5 min
No.
Name
Description
Value
Explanation
Default
value