9  Troubleshooting

Operating Manual

SI30M-44M-60H-80H-BE-en-30

61

W 778 DSPNoSlv1

1

CAN communication with slave 1 is

faulty.

Ensure that undamaged CAT5e

cables are used for communication

and that the cables are plugged in

correctly.

Ensure that the communication bus

is equipped with a terminator at

both ends.

W 779 DSPNoSlv2

1

CAN communication with slave 2 is

faulty.

F 781 SlvError

4

Error at a slave in the main cluster

causing system shutdown.

Read off the pending and logged

warnings and errors and eliminate

the causes.

F 782 AIVtgMonFail

4

Monitoring of the utility grid has

failed.

• Contact the SMA Service Line.

F 783 CANCom

2

Synchronization in the cluster is

interrupted at the master.

Ensure that undamaged CAT5e

cables are used for communication

and that the cables are plugged in

correctly.

Ensure that the communication bus

is equipped with a terminator at

both ends.

W 784 CANComSlv1

1

Synchronization in the cluster is

interrupted at slave 1.

W 785 CANComSlv2

1

Synchronization in the cluster is

interrupted at slave 2.

F 787 VcoreFail

3

Internal device voltage in the master

is outside the tolerance limits.

• Contact the SMA Service Line.

F 788 VcoreFailSlv1

3

Internal device voltage in slave 1 is

outside the tolerance limits.

F 789 VcoreFailSlv2

3

Internal device voltage in slave 2 is

outside the tolerance limits.

W 791 RsDspSlv1

1

Signal processor has performed a

reset.

W 792 RsDspSlv2

1

W 793 TimeOutDspSlv1

1

Time for performing a particular task

has been exceeded.

W 794 TimeOutDspSlv2

1

W 797 AiVtgMonFailSlv1 1

Monitoring of the utility grid has

failed.

W 798 AiVtgMonFailSlv2 1

No.

Name

Level Cause

Corrective measures