9 Troubleshooting
Operating Manual
SI30M-44M-60H-80H-BE-en-30
61
W 778 DSPNoSlv1
1
CAN communication with slave 1 is
faulty.
•
Ensure that undamaged CAT5e
cables are used for communication
and that the cables are plugged in
correctly.
•
Ensure that the communication bus
is equipped with a terminator at
both ends.
W 779 DSPNoSlv2
1
CAN communication with slave 2 is
faulty.
F 781 SlvError
4
Error at a slave in the main cluster
causing system shutdown.
•
Read off the pending and logged
warnings and errors and eliminate
the causes.
F 782 AIVtgMonFail
4
Monitoring of the utility grid has
failed.
• Contact the SMA Service Line.
F 783 CANCom
2
Synchronization in the cluster is
interrupted at the master.
•
Ensure that undamaged CAT5e
cables are used for communication
and that the cables are plugged in
correctly.
•
Ensure that the communication bus
is equipped with a terminator at
both ends.
W 784 CANComSlv1
1
Synchronization in the cluster is
interrupted at slave 1.
W 785 CANComSlv2
1
Synchronization in the cluster is
interrupted at slave 2.
F 787 VcoreFail
3
Internal device voltage in the master
is outside the tolerance limits.
• Contact the SMA Service Line.
F 788 VcoreFailSlv1
3
Internal device voltage in slave 1 is
outside the tolerance limits.
F 789 VcoreFailSlv2
3
Internal device voltage in slave 2 is
outside the tolerance limits.
W 791 RsDspSlv1
1
Signal processor has performed a
reset.
W 792 RsDspSlv2
1
W 793 TimeOutDspSlv1
1
Time for performing a particular task
has been exceeded.
W 794 TimeOutDspSlv2
1
W 797 AiVtgMonFailSlv1 1
Monitoring of the utility grid has
failed.
W 798 AiVtgMonFailSlv2 1
No.
Name
Level Cause
Corrective measures