SMA SI 3.0-11 User Manual
Page 111

SMA Solar Technology AG
13 Directory of the Parameters in Installer Mode and Expert Mode
Operating Manual
SI30M-44M-60H-80H-BE-en-30
111
234# Gen Control
No.
Name
Description
Value
Explanation
Default
value
234.01 GnVtgMin
Minimum generator
voltage in V
(expert mode)
172.5 V to
210.01 InvVtgNom
‒
✖ ✓ 172.50 V
234.02 GnVtgMax
Maximum generator
voltage in V
(expert mode)
210.01 InvVtgNom
to 264.5 V
‒
✖ ✓ 250.0 V
234.03 GnCurNom
Nominal generator
current in A
0.0 A to 50.0 A
One Sunny Island ✖ ✓ 16.0 A
0.0 A to 100.0 A
Two Sunny Island
inverters, parallel
16.0 A
0.0 A to 150.0 A
Three
Sunny Island
inverters, parallel
16.0 A
0.0 A to 50.0 A
Three-phase
16.0 A
0.0 A to 80.0 A
Multicluster Box 6
60.0 A
0.0 A to 160.0 A
Multicluster Box
12
160.0 A
0.0 A to 500.0 A
Multicluster Box
36
435.0 A
234.04 GnFrqNom
Nominal generator
frequency under nominal
load in Hz (expert mode)
234.05 GnFrqMin
to
234.06 GnFrqMax
230 V/50 Hz
✖ ✓ 50.00
Hz
220 V/60 Hz
60.00
Hz
234.05 GnFrqMin
Minimum generator
frequency in Hz
(expert mode)
40.00 Hz to
234.04 GnFrqNom
230 V/50 Hz
✖ ✓ 44.64
Hz
50.00 Hz to
234.04 GnFrqNom
220 V/60 Hz
50.00
Hz
234.06 GnFrqMax
Maximum generator
frequency in Hz
(expert mode)
234.04 GnFrqNom
to 70.00 Hz
230 V/50 Hz
✖ ✓ 60.00
Hz
220 V/60 Hz
70.00
Hz
234.07 GnStrMod
Generator interface
Manual
Manual
✖ ✓ Autostart
Autostart
Automatic
234.08 GnOpTmMin
Minimum run time of
generator in minutes
0 min to 360 min
‒
✖ ✓ 15 min
234.09 GnStpTmMin
Minimum stop time of the
generator in minutes
0 min to 360 min
‒
✖ ✓ 15 min
234.10 GnCoolTm
Cooling time of the
generator in minutes
0 min to 60 min
‒
✖ ✓ 5 min