SMA SI 3.0-11 User Manual
Page 106

13 Directory of the Parameters in Installer Mode and Expert Mode
SMA Solar Technology AG
106
SI30M-44M-60H-80H-BE-en-30
Operating Manual
232.05 GdFrqNom
Nominal grid frequency
in Hz (expert mode,
protected by SMA Grid
Guard)
232.05
GdFrqMin to
232.06
GdFrqMax
230 V/50 Hz
✓ ✓ 50.00 Hz
220 V/60 Hz
60.00 Hz
232.06 GdFrqMin
Minimum power
frequency in Hz (expert
mode, protected by
SMA Grid Guard)
40.00 Hz to
232.04
GdFrqNom
230 V/50 Hz
✓ ✓ 47.50 Hz
220 V/60 Hz
59.30 Hz
232.07 GdFrqMax
Maximum power
frequency in Hz (expert
mode, protected by
SMA Grid Guard)
232.4GdFrqNom
to 70.00 Hz
230 V/50 Hz
✓ ✓ 51.50 Hz
220 V/60 Hz
60.50 Hz
232.08 GdVldTm
Minimum observation
time for line voltage and
frequency in the
permissible range for
connection in s (expert
mode, protected by
SMA Grid Guard)
5 s to 900 s
VDE-AR-N 4105
AS4777
✓ ✓ 60 s
220 V/60 Hz
300 s
232.09 GdMod
Grid interface (expert
mode, protected by
SMA Grid Guard)
GridCharge
Charge on utility
grid
✓ ✓ −
GridFeed
Charge and
feedback on utility
grid
232.10 GdRvPwr
Permissible active power
of grid reverse power
in W (expert mode)
0 W to 5,000 W One Sunny Island
or single-cluster
system
✖ ✓ 100 W
0 W to
20,000 W
Multicluster
system
100 W
232.11 GdRvTm
Permissible time for grid
reverse power in s
(expert mode)
0 s to 60 s
‒
✖ ✓ 5 s
232.12 GdVtgMinDel
Lower voltage difference
for valid grid connection
in V
(expert mode, protected
by SMA Grid Guard)
0.0 V to 20.0 V
VDE_AR_4105
✓ ✓ 11.5 Hz
AS4777
2.0 Hz
Off-grid
2.0 Hz
Other
2.0 Hz
220 V/60 Hz
2.0 Hz
232.13 GdVtgMaxDel Upper voltage difference
for valid grid connection
in V
(expert mode, protected
by SMA Grid Guard)
0.0 V to 12.0 V
VDE_AR_4105
✓ ✓ 11.5 Hz
AS4777
2.0 Hz
Off-grid
2.0 Hz
Other
2.0 Hz
220 V/60 Hz
2.0 Hz
No.
Name
Description
Value
Explanation
Default
value