9  Troubleshooting

SMA Solar Technology AG

46

SI30M-44M-60H-80H-BE-en-30

Operating Manual

9.4 Logged Warning Messages and Error Messages

9.4.1 Sunny Island Category (1xx)

No.

Name

Level Cause

Corrective measures

F 109 InvTmpHi

3

Temperature of the transformer in

the master is too high due to

overload or ambient temperature.

• Ensure that the Sunny Island is

functional. For this, wait until the

Sunny Island has cooled down

and then restart it.

• Clean the fans (see Section 10.7

"Cleaning the Fans", page 77).

• Reduce the total power of the

loads, e.g., by staggering their use

over time.

W 110 InvTmpHiSlv1

1

Temperature of the transformer in

slave 1 is too high due to overload

or ambient temperature.

W 111 InvTmpHiSlv2

1

Temperature of the transformer in

slave 2 is too high due to overload

or ambient temperature.

F 113 InvTmpHi

3

Temperature of the heat sink in the

master is too high due to overload

or ambient temperature.

• Ensure that the Sunny Island is

functional. For this, wait until the

Sunny Island has cooled down

and then restart it.

• Reduce the total power of the

loads, e.g., by staggering their use

over time.

W 114 InvTmpHiSlv1

1

Temperature of the heat sink in

slave 1 is too high due to overload

or ambient temperature.

W 115 InvTmpHiSlv2

1

Temperature of the heat sink in

slave 2 is too high due to overload

or ambient temperature.

F 117 AcCurLim

2

The power of the loads is too high

for the master.

• Ensure that the Sunny Island is

functional. For this, clean the fans

and restart the Sunny Island (see

Section 10.7 "Cleaning the Fans",

page 77).

Ensure that there are no short

circuits in the system and that the

power of the loads is not greater

than the power of the

Sunny Island inverter.

Use a star delta electronic circuit

to start three-phase loads with a

high start-up electricity demand

(e.g., engines).

Connect the loads with very high

power directly to the generator

whenever possible. Ensure that the

generator is not overloaded.

W 118 AcCurLimSlv1

1

The power of the loads is too high

for slave 1.

W 119 AcCurLimSlv2

1

The power of the loads is too high

for slave 2.