SMA SI 3.0-11 User Manual
Page 55

SMA Solar Technology AG
9 Troubleshooting
Operating Manual
SI30M-44M-60H-80H-BE-en-30
55
F 365 VAcExtPhsFail
3
The line conductors of the
measured AC voltage at
connections VExt and AC2
do not match.
• Ensure that the neutral conductor and line
conductor are correctly connected to
connection ExtVtg.
• Ensure that the neutral conductor and line
conductor are correctly connected to
connection AC2.
• Ensure that the connections ExtVtg and
AC2 are connected to the same line
conductor.
F 366 HotAcBus
3
When the tie switch is open,
AC voltage from an
unknown source is present at
connection AC2.
• Ensure that the triggering of the tie switch
is correct.
• Ensure that the tie switch is correctly
wired.
F 367 ExtCtcNotOpen
3
Tie switch does not open.
• Ensure that the triggering of the tie switch
is correct.
• Ensure that the tie switch is correctly
wired.
• Ensure that the feedback contact is
correctly connected.
F 368 NRelNotOpen
3
Neutral conductor relay of
the master does not open.
• Contact the SMA Service Line.
W 369 NRelNotOpenSlv1 1
Neutral conductor relay of
slave 1 does not open.
W 370 NRelNotOpenSlv2 1
Neutral conductor relay of
slave 2 does not open.
W 372 VtgFrqRatio
1
Disconnection from the utility
grid or generator due to
noncompliance with the
voltage-frequency ratio at
the master
• Contact the SMA Service Line if required.
W 373 VtgFrqRatioSlv1
1
Disconnection from the utility
grid or generator due to
noncompliance with the
voltage-frequency ratio at
slave 1
W 374 VtgFrqRatioSlv2
1
Disconnection from the utility
grid or generator due to
noncompliance with the
voltage-frequency ratio at
slave 2
No.
Name
Level Cause
Corrective measures