9  Troubleshooting

Operating Manual

SI30M-44M-60H-80H-BE-en-30

55

F 365 VAcExtPhsFail

3

The line conductors of the

measured AC voltage at

connections VExt and AC2

do not match.

• Ensure that the neutral conductor and line

conductor are correctly connected to

connection ExtVtg.

• Ensure that the neutral conductor and line

conductor are correctly connected to

connection AC2.

• Ensure that the connections ExtVtg and

AC2 are connected to the same line

conductor.

F 366 HotAcBus

3

When the tie switch is open,

AC voltage from an

unknown source is present at

connection AC2.

• Ensure that the triggering of the tie switch

is correct.

• Ensure that the tie switch is correctly

wired.

F 367 ExtCtcNotOpen

3

Tie switch does not open.

• Ensure that the triggering of the tie switch

is correct.

• Ensure that the tie switch is correctly

wired.

• Ensure that the feedback contact is

correctly connected.

F 368 NRelNotOpen

3

Neutral conductor relay of

the master does not open.

• Contact the SMA Service Line.

W 369 NRelNotOpenSlv1 1

Neutral conductor relay of

slave 1 does not open.

W 370 NRelNotOpenSlv2 1

Neutral conductor relay of

slave 2 does not open.

W 372 VtgFrqRatio

1

Disconnection from the utility

grid or generator due to

noncompliance with the

voltage-frequency ratio at

the master

• Contact the SMA Service Line if required.

W 373 VtgFrqRatioSlv1

1

Disconnection from the utility

grid or generator due to

noncompliance with the

voltage-frequency ratio at

slave 1

W 374 VtgFrqRatioSlv2

1

Disconnection from the utility

grid or generator due to

noncompliance with the

voltage-frequency ratio at

slave 2

No.

Name

Level Cause

Corrective measures