13  Directory of the Parameters in Installer Mode and Expert Mode

Operating Manual

SI30M-44M-60H-80H-BE-en-30

117

242# Load

241.01 Rly1Op Multifunction

relay 1 function

(continued)

SiComRemote Multifunction relay is controlled via

ComSync.

✓ ✓ AutoGn

Overload

When the Sunny Island limits its

power, the multifunction relay is

deactivated.

GriSwt

Triggering of contactors for grid

disconnection in the battery backup

system

GndSwt

Triggering of the grounding in the

battery backup system

241.02 Rly2Op Multifunction

relay 2 function

See 241.01 Rly1Op, page 115 for value and

explanation

✓ ✓ AutoLodExt

No.

Name

Description

Value

Default

value

241.07 ExtPwrDerMinTm

Minimum time for the ExtPwrDer function of the

multifunction relay in minutes

0 min to

600 min

✓ ✓ 10 min

241.08 ExtPwrDerDltVtg

Voltage difference for the ExtPwrDer function of

the multifunction relay in V
The voltage difference corresponds to the cell

voltage of the battery.

0 V to

0.40 V

✓ ✓ 0.15 V

No.

Name

Description

Value

Default

value

242.01 Lod1SocTm1Str SOC threshold for starting load

shedding 1 in interval 1 in %
Interval 1 begins at time

242.05 Lod1Tm1Str.

1% to 242.02

Lod1SocTm1Stp

✓ ✓ 30%

242.02 Lod1SocTm1Stp SOC threshold for stopping load

shedding 1 in interval 1 in %
Interval 1 begins at time

242.05 Lod1Tm1Str.

242.01 Lod1SocTm1Str

to 90%

✓ ✓ 50%

242.03 Lod1SocTm2Str SOC threshold for starting load

shedding 1 in interval 2 in %
Interval 2 begins at time

242.06 Lod1Tm2Str.

1% to 242.04

Lod1SocTm2Stp

✓ ✓ 30%

242.04 Lod1SocTm2Stp SOC threshold for stopping load

shedding 1 in interval 2 in %
Interval 2 begins at time

242.06 Lod1Tm2Str.

242.03 Lod1SocTm2Str

to 90%

✓ ✓ 50%

242.05 Lod1Tm1Str

Start of interval 1 for load shedding 1

in hh:mm:ss

00:00:00 to 23:59:59

✓ ✓ ‒

No.

Name

Description

Value

Explanation

Default

value