Handling of pending errors upon activation

During the activation procedure, all pending errors are acknowledged without the error being logged in the list 420#

Error history. Errors which are still pending are entered again after activation. Errors which were detected by the

Sunny Island before activation and are no longer detected after activation are shown in the list 420# Error history.

Autostart

The autostart function allows automatic restarts in the event of malfunctions. If the autostart function fails in the event of a

malfunction, the Sunny Island attempts to carry out the next autostart immediately. The number of autostarts is restricted.

If the Sunny Island is in operation without malfunctions for ten minutes, it resets the autostart counter.
When the maximum number of autostarts has been reached, the Sunny Island reacts as follows:

• The Sunny Island waits ten minutes.
• The autostart counter is reset.
• The Sunny Island attempts to perform an autostart.
• When the maximum number of autostarts has been reached, the Sunny Island waits again for ten minutes.

9.2 Acknowledging Errors

If a malfunction or failure occurs, the Sunny Island switches to standby mode. Once you have eliminated the cause of the

error, you can enable a restart of the Sunny Island inverter by acknowledging the error.

Procedure:

1. Eliminate the cause.
2. Press the button on the Sunny Remote Control. This acknowledges the error.
3. Start the system (see Section 4.2, page 18).

9.3 Logged Events

9.3.1 Sunny Island Category (1xx)

4

Failure

Failure

Device failure, the Sunny Island switches off. Troubleshooting,

acknowledgment of the error and manual restart necessary.

5

Device defect

Defect

The Sunny Island is defective and switches itself off. The Sunny Island

must be replaced.

No.

Name

Description

E101 Standby

Waiting mode

E102 Startup

Startup process

E103 Run

Operation

E104 RunExtGn

Operation with a generator

E105 RunExtGd

Operation with the utility grid

E106 RunGdFeed

Feed-in grid operation

E108 Silent

Energy saving mode

E110 ErrShutdown

Shutdown due to error

Level

Designation

Display on the

Sunny Remote

Control

Explanation