13 Directory of the Parameters in Installer Mode and Expert Mode
Operating Manual
SI30M-44M-60H-80H-BE-en-30
113
235# Gen Start
No.
Name
Description
Value
Explanation
Default
value
235.01 GnAutoEna
Automatic restart of
generator in the event of
disturbance
Off
Disable
✖ ✓ On
On
Enable
235.02 GnAutoStr
Number of attempts to carry
out automatic restart of
generator (expert mode)
0 to 10
‒
✖ ✓ 3
235.03 GnSocTm1Str
SOC threshold for generator
request in interval 1 in %
Interval 1 begins at time
235.07 GnTm1Str
1% to 235.04
GnSocTm1Stp
‒
✖ ✓ 40%
235.04 GnSocTm1Stp
SOC threshold for end of
generator request in interval
1 in %
Interval 1 begins at time
235.07 GnTm1Str.
235.03
GnSocTm1Str
to 95%
‒
✖ ✓ 80%
235.05 GnSocTm2Str
SOC threshold for generator
request in interval 2 in %
Interval 2 begins at time
235.08 GnTm2Str.
1% to 235.06
GnSocTm2Stp
‒
✖ ✓ 40%
235.06 GnSocTm2Stp
SOC threshold for end of
generator request in interval
2 in %
Interval 2 begins at time
235.08 GnTm2Str.
235.05
GnSocTm2Str
to 95%
‒
✖ ✓ 80%
235.07 GnTm1Str
Start of interval 1 for grid
request in hh:mm:ss
00:00:00 to
23:59:59
‒
✖ ✓ 00:00:00
235.08 GnTm2Str
Start of interval 2 for grid
request in hh:mm:ss
00:00:00 to
23:59:59
‒
✖ ✓ 00:00:00
235.09 GnPwrEna
Load-dependent generator
request (expert mode)
Disable
Disable
✖ ✓ Enable
Enable
Enable
235.10 GnPwrStr
Threshold for
load-dependent generator
request in kW (expert mode)
235.11GnPwrStp
to 300.0 kW
‒
✖ ✓ 4.0 kW
235.11 GnPwrStp
Threshold for end of
load-dependent generator
request, in kW
(expert mode)
0.0 kW to
235.10 GnPwrStr
‒
✖ ✓ 2.0 kW
235.12 GnPwrAvgTm
Averaging time for
load-dependent generator
request in s (expert mode)
1 s to 900 s
‒
✖ ✓ 60 s
235.13 GnTmOpEna
Time-controlled generator
operation
Disable
Disable
✖ ✓ Disable
Enable
Enable