13  Directory of the Parameters in Installer Mode and Expert Mode

SMA Solar Technology AG

104

SI30M-44M-60H-80H-BE-en-30

Operating Manual

225# Current Sensor

13.2.3 External/Backup (230#)

231# General

No.

Name

Description

Value

Explanation

Default value

225.01 BatCurSnsTyp

Type of battery current

sensor

None

No sensor is

connected

✓ ✓ None

60 mV

60 mV type

50 mV

50 mV type

225.02 BatCurGain60

60 mV type in

A

60 mV

0

A

60 mV

to

1,800

A

60 mV

✓ ✓ 100

A

60 mV

225.03 BatCurGain50

50 mV type in

A

50 mV

0

A

50 mV

to

1,800

A

50 mV

✓ ✓ 100

A

50 mV

225.04 BatCurAutoCal

Automatic calibration

of external battery

current sensor

Start

Start automatic

calibration

✓ ✓ ‒

No.

Name

Description

Value

Explanation

Default

value

231.01 PvFeedTmStr Start time for PV grid

feed-in in hh:mm:ss

(expert mode)

00:00:00

to

23:59:59

✖ ✓ 04:00:00

231.02 PvFeedTmStp Stop time for PV grid

feed-in in hh:mm:ss

(expert mode)

00:00:00

to

23:59:59

✖ ✓ 22:00:00

231.03 ExtLkTm

Lock time after reverse

power or relay protection

in minutes (expert mode)

0 min to

60 min

✖ ✓ 20 min

231.06 ExtSrc

Generator- and grid

operating mode

PvOnly

Only AC sources in the

stand-alone grid,

no generator in the off-grid

system

✖ ✓ ‒

Gen

Generator

Grid

Utility grid

GenGrid Electric generator or utility

grid

231.12 ClstPwrNom Nominal power of the

cluster in kW

✓ ✓ ‒