Installation and Setup

98

Site Preparation - IMG 1004

Topic Location: IMG 1004-Installation and Setup Guide > IMG 1004-Hardware

Installation

Ensure that the following requirements are met before you begin installation.

Important: Any variances from the mutually agreed upon site preparation

details (such as power cabling, network cabling, equipment room readiness) may

affect installation scheduling.

Site Preparation Checklist

Requirements

Completed

Location

Spacing

Mounting

Power

Electromagnetic Interference

Channel Service Units

Electrostatic Discharge

Protection

Location

The 120/240 V AC unit does not have to be located in a restricted area. It can be

located in a clean and well ventilated office space.

Spacing

There are no spacing requirements.

Mounting

The IMG 1004 can be mounted in a 19-inch rack. The mounting brackets can be

mounted at either the front or the rear of the IMG 1004 chassis.

If mounting multiple IMG 1004's in a rack, ensure that

a hazardous condition does not exist due to uneven

mechanical loading.

Avoid mounting inside a cabinet with closed doors

unless you can provide sufficient ventilation inside the

cabinet. Elevated operating ambient conditions may

occur in an enclosed equipment rack. The operating

ambient temperature may be greater than the room

temperature.

Do not block the front of the chassis doing so can cause

the unit to overheat.