2.2 Mounting

If the CDM-700 is to be mounted in a rack, ensure that there is adequate clearance for ventilation,
particularly at the sides. In rack systems where there is high heat dissipation, forced air-cooling
must be provided by top or bottom mounted fans or blowers. Under no circumstance should the
highest internal rack temperature be allowed to exceed 50°C (122°F).

IMPORTANT

The CDM-700 has short rear support brackets mounted to the side of the
chassis -
two cooling fans are mounted on the right-hand side of the unit.

2.2.1 Method A: Optional Rear-Mounting Support Brackets

Install the optional rear-mounting support brackets (Figure 2-1) using mounting kit KT/6228-2:

Mounting Kit KT/6228-2 (Optional)

Quantity

Part Number

Description

2

HW/10-32SHLDR

Screw, #10 Shoulder

4

HW/10-32FLT

Washer, #10 Flat

2

HW/10-32SPLIT

Washer, #10 Split

2

HW/10-32HEXNUT

Nut, #10 Hex

2 FP/6138-1

Bracket,

Rear

Support

4

HW/10-32x1/2RK

Bolt, #10 Rack Bracket

The tools required for this installation are a medium Phillips

™ screwdriver and a

5/32-inch SAE Allen

™ Wrench.


The CDM-700 is assembled into the equipment rack as follows:

Step

Procedure

1

Secure the #10 shoulder screws to the unit chassis through the rear
right and left side mounting slots, using the #10 flat washers, #10
split washers, and #10 hex nuts as shown.

2

Install the rear support brackets onto the equipment rack
threaded rear mounting rails, using the #10 rack bracket bolts.

3

Mount the unit into the equipment rack, ensuring that the shoulders
of the #10 shoulder screws properly engage into the rear support
bracket slots.