S-0-0907 control word dynamic mdt, Output cycle counter, Rsvd – BECKHOFF AX5000 S-IDN Parameters User Manual
Page 187

SIDNs
S00907 Control word dynamic MDT
The parameter contains the control word for the dynamic master data telegram (dynamic MDT).
Attributes
Name
Value
Format
BINARY
Data length
16
Decimal point
0
Min value
Max value
Default value
Unit
Changeable in EtherCAT state
In PreOp, SafeOp and Op
Cyclic transfer
No
Device parameter
No
Related to interface revision
from 204
This control word can be transferred to the drive in the dynamic master data telegram. This control word
enables the drive to detect telegram failures.
Note
Nested structure
Note the nesting depth and the structure information at the start of the descriptions.
Output cycle counter
S00907Control word dynamic MDT / Output cycle counter
Bit pattern:
Bit Meaning
01 Output cycle counter
This counter should be incremented by the controller in each communication cycle.
215 Reserved
Format
Size in bits
Offset
UINT2
2
0
rsvd
S00907Control word dynamic MDT / rsvd
Format
Size in bits
Offset
UINT14
14
2
AX5000 IDNDescriptions
187
Version 3.1