Two-channel, digital input terminals, 24 V
DC
The KL1002 and KL1012 digital input terminals acquire the binary control signals from the process level and transmit
them, in an electrically isolated form, to the higher-level automation unit. The KL1002 and KL1012 versions have input
filters of different speeds. The Bus Terminals contain two channels that indicate their signal state by means of light
emitting diodes.
Technical data
KL1002/KS1002
KL1012/KS1012
Connection technology
4-wire
Number of inputs
2
Rated voltage
24 V
DC
(-15%/+20%)
Signal voltage “0”
-3 V … +5 V
Signal voltage “1”
+15 V … +30 V
Input filter
3 ms
0.2 ms
Input current
typically 5 mA
Current consumption from K-bus
typically 3 mA
Electrical isolation
500 V (K-Bus/field potential)
Bit width in process image
2 input bits
Configuration
no address-or configuration settings required
Dimensions (W x H x D)
15mm x 100mm x 70mm (connected width: 12mm)
Weight
approx. 50 g
during operation
-25°C ... +60°C
0°C ... +55°C (according to cULus, for Canada and USA)
0°C ... +55°C (according to ATEX, see special conditions)
Permissible ambient
temperature range
during storage
-40°C... +85°C
Relative humidity
5% ... 95%, no condensation
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC resistance/emission
conforms to EN 61000-6-2 / EN 61000-6-4