S00159 Monitoring window
This parameter specifies the maximum permissible deviation between the set and actual positions. If this
difference, which is also referred to as position lag, exceeds the value specified in this parameter, the drive
sets the C1D error bit 11 of S00011.
Attributes
Name
Value
Format
udec
Data length
32
Decimal point
0
Min value
0
Max value
4 294 967 295
Default value
0
Unit
inc
Changeable in EtherCAT state
PreOp, SafeOp, Op
Cyclic transfer
No
Device parameter
No
Related to interface revision
No
Following error monitoring in the AX5000 is only active if the value of S00159 > 0. If the higherlevel
controller (NC) monitors the following error (S00189), this parameter can be left at the "default" value of
zero. If the controller does not deal with this task, a value adapted to the application must be specified here.
Note
IDNs involved
AX5000 IDNDescriptions
117
Version 3.1
- Bus Terminal System (19 pages)
- EP-xxxx-xxxx (19 pages)
- BK2000 (30 pages)
- LC3100 (67 pages)
- BK4000 (28 pages)
- BK3xx0 (95 pages)
- BK5000 (12 pages)
- LC5200 (32 pages)
- BK7000 (29 pages)
- BK7500 (32 pages)
- BK7300 (40 pages)
- BK8100 (26 pages)
- BC2000 (28 pages)
- BC3100 (51 pages)
- BC7300 (48 pages)
- BC8100 (36 pages)
- BC3150 (112 pages)
- KL1012 (2 pages)
- KL1114 (2 pages)
- KL1164 (1 page)
- KL1232-xxxx (4 pages)
- KL1501 (19 pages)
- KL1512 (15 pages)
- KL2521-0024 (18 pages)
- KL2512 (21 pages)
- KL2612 (4 pages)
- KL2622 (9 pages)
- KL3062 (24 pages)
- KL3064 (20 pages)
- KL4132 (19 pages)
- KL4034 (25 pages)
- KL3302 (23 pages)
- KL3351 (18 pages)
- KS3681 (43 pages)
- KL4112 (18 pages)
- KL5001 (16 pages)
- KL5051 (17 pages)
- KL5101-0012 (21 pages)
- KS5111-0000 (21 pages)
- KL5121 (19 pages)
- KL6021 (20 pages)
- KL6051 (17 pages)
- Z1000 (2 pages)
- KL6071 (12 pages)
- Z1003 (2 pages)