BECKHOFF AX5000 S-IDN Parameters User Manual
Page 115

SIDNs
S00149 Positive drive stop procedure command (pc)
The parameter contains the command: "Travel to fixed stop". This command disables following error
monitoring of the drive.
Attributes
Name
Value
Format
binary
Data length
16
Decimal point
0
Min value
Max value
Default value
Unit
Changeable in EtherCAT state
SafeOp and Op
Cyclic transfer
No
Device parameter
No
Related to interface revision
“Set and activate command” results in all monitoring being switched off, which otherwise would lead to a
drive error S00011 (drive shut down) if the drive is blocked by a fixed stop.
The command is confirmed positively if the following is true:
– |T | ≥ |Tlimit| (T_limit corresponds to the effective maximum or minimum of Sx0092, Sx0082, and Sx
0083 here.)
– The actual speed is the standstill window (nfeedback = 0 )
Upon completion of the command, all monitoring is restored to the original state.
Bit pattern:
Bit Meaning
0
Cancel cmd
Cancel command
0 = disable
1 = enable
1
Set cmd
Set command
0 = disable
1 = enable
2
Reserved
3
Set & enable command
Set & enable command
0 = disable
1 = enable
4
15
Reserved
Note
IDNs involved
S00011, S00189
AX5000 IDNDescriptions
115
Version 3.1