External Trigger input is standard.
Line sync and External sync are mutually exclusive.
External Trigger input and External sync are mutually exclusive.
Units with -LKS (auxiliary) cannot have Line Sync or External Sync.

2.6.1 -HV Option Lx Series - Supplemental Specifications

Specifications for Lx units with -HV voltage range option installed are same as standard Lx unit
except where noted below.

Voltage:

Ranges (L-N):

Low range

0 - 135 Vrms

High range

0 - 270 Vrms

Maximum Current at Full Power

Note: Current, maximum amps per phase available at on low voltage range. 3000Lx and 4500Lx

operate in constant power mode up to currents shown at reduced voltage. See Figure 2-1.
For 9000Lx/2 and 12000Lx/2, currents are 2 x 4500Lx and 6000Lx.
For 13500Lx/3 and 18000Lx/3, currents are 3 x 4500Lx and 6000Lx

Model

3000Lx-HV

4500Lx-HV

6000Lx-HV

Single Phase Mode:
Max. RMS, low Vrange

44.4 A

44.4 A

44.4 A

Three Phase Mode:
Max. RMS, low Vrange
per phase

14.8 A

14.8 A

14.8 A

Note:

Current derates linearly from 50% of voltage range to 20% of specified current at 10% of
voltage range.
Current in High voltage range is reduced by a factor of 2.

Note:

For 9000Lx/2-HV and 12000Lx/2-HV, currents are 2 x 4500Lx-HV and 6000Lx-HV.
For 13500Lx/3-HV and 18000Lx/3-HV, currents are 3 x 4500Lx-HV and 6000Lx-HV

Maximum Current at Full Scale Voltage

Model

3000Lx-HV

4500Lx-HV

6000Lx-HV

Single Phase Mode:
Max. RMS, low Vrange

22.2 A

33.3 A

44.4 A

Three Phase Mode:
Max. RMS, low Vrange
per phase

7.4 A

11.1 A

14.8 A