Specifications, 1 electrical – AMETEK Lx Series II User Manual

Page 17

background image

User Manual

Lx / Ls Series II

13

2. Specifications

Specifications shown are valid over an ambient temperature range of 25 5 C and apply after a
30 minute warm-up time. Unless otherwise noted, all specifications are per phase for sine wave
output into a resistive load. For three phase configurations or mode of operation, all
specifications are for Line to Neutral (L-N) and phase angle specifications are valid under
balanced load conditions only.

Specifications for Ls models are identical to those for the Lx except where noted.

2.1 Electrical

2.1.1 Input

Parameter

Specification

Line Voltage:
(3 phase, 3 wire
+ ground (PE))

3000Lx, 4500Lx, 9000Lx/2, 13500Lx/3:
Std:

208 - 230 VLL ± 10%

-400:

400 V

LL

10%

-480

480 V

LL

5%

6000Lx, 12000Lx/2, 18000Lx/3:
Std:

208 - 230 VLL + 10%

1

Note: Each Lx/ Ls chassis requires
its own AC service.

Note: 3000Lx/Ls may be operated
from 208-230 V L-N single phase
AC input between L2 and L3 on
TB3 for3000Lx or ØB- ØC on TB3
for 3000Ls.

Line VA:
(total)

3000Lx / Ls

5900 VA / 4100 W

4500Lx / Ls

8900 VA / 5900 W(x2 for 9000Lx/2, x3 for 13500Lx/3)

6000Lx / Ls

11900 VA / 7900 W (x2 for 12000Lx/2, x3 for 18000Lx/3

Line Current:
(per phase)

3000Lx / Ls

Std: 19 Arms @ 187 VLL, 3 phase AC input.
[32 Arms @ 187 VLN single phase AC input. Connect
between TB3 L2-L3 on 3000Lx or TB3

ØB- ØC on

3000Ls

]

-400: 10 Arms @ 360 VLL, 3 phase AC input.

4500Lx / Ls

Std: 31 Arms @ 187 VLL

-400: 16 Arms @ 360 VLL

-480: 13 Arms @ 456 VLL

6000Lx / Ls

Std: 38 Arms @ 208 VLL

Currents shown are for single chassis models. For multi-chassis
configurations, currents are per chassis.

1

Note that operation below 208V L-L AC input is available with the following derating considerations:

1) If operating at less than a 5000 VA output power there will be no affect on the output.
2) If operating in 3-phase mode, with a full-scale output voltage and a frequency less than three times the line
frequency, the voltage distortion may exceed specification between 5500 and 6000 VA output.
3) If operating in 1-phase mode above 5000 VA, above 85% of full-scale output voltage and an output frequency
less than three times the line frequency, the voltage distortion may exceed specification and the output may fault
with a crest factor load more than 2.
In most applications, these conditions are not likely to exits. At AC input voltages of 208 V or higher, the 6000Lx/Ls
meets specifications under all conditions.