Lx / Ls Series II

180

TAC 501 Tests

Starting operations are not applicable to AC Utilization Equipment.

TAC 601 Tests

– Revision F only.

TAC601

Power Failure - One Phase

Condition

Duration (s)

A

100 msec

52

B

500 msec

54

C

3 sec

66

D

7 sec

86

TAC 602 Tests

– Revision F only.

TAC601

Power Failure

– One, Two Phase

Condition

Duration (s)

One Phase

A

Phase A, 7 sec - 5x

86

B

Phase B, 7 sec - 5x

86

C

Phase C, 7 sec - 5x

86

D

Phase A, 30 min - 1x

1800

E

Phase B, 30 min - 1x

1800

F

Phase C, 30 min - 1x

1800

Two Phase

G

Phase A&B, 7 sec - 5x

86

H

Phase B&C, 7 sec - 5x

86

I

Phase A&B, 30 min - 1x

1800

J

Phase B&C, 30 min - 1x

1800

TAC 603 Tests

– Revision F.

TAC603

Power Failure

– Phase Reversal

Condition

Duration (s)

A

Phase rotation C-B-A

1800

Phase rotation A-B-C

1800