beautypg.com

AMETEK Lx Series II User Manual

Page 117

background image

User Manual

Lx / Ls Series II

113

8. Repeat the entry for Phase C. Make sure the ENTER key is pressed each time a value

has to be reset to the factory default setting to store this value

9. If three-phase mode is available, select the three-phase mode from the

CONFIGURATION menu. If the Ls unit has one-phase only, adjust only phase A.

10. Select the Low Voltage range.

11. Select the SETUP screen and scroll to the ALC setting entry. Turn off the ALC mode by

selecting OFF and then set the program value for the output voltage for all three phases
to 115.00 volts and 400 Hz with respect to Neut (Ls) or Com (Lx).

12. Close the output relay.

13. Connect the external AC DVM to the respective output and use the adjustment indicated

below so set the output voltage to 115 0.115 volts.

14. Repeat for Phase B and C as needed.

15. Open the output relays when done.

Output

Phase

Current Limit

Board

Adjustment Pots

OUTP CAL value

Standard

-HF option

A or 1

R1

450

450

B or 2

R2

450

450

C or 3

R3

450

450

Table 6-4: Output Calibration Coefficients - Factory Defaults.