Kipp&Zonen COMBILOG Data Logger User Manual
Page 98
If no other specifications are made on delivery, the data logger
has address 1 and baud rate 19,200 bps, no parity as default.
The adjustment can be changed via bus by means of the con-
figuration software COMBILOG.EXE:
Adjustment via bus by means of the configuration soft-
ware:
The condition for adjusting address and baud rate via bus is
that there are no different data loggers with the same address
on the bus. Otherwise the bus connection has to be disconnec-
ted or the supply voltage has to be interrupted for the duration
of the adjustment with those data loggers having the same ad-
dress as the data logger that is to be newly adjusted. The data
logger to be newly adjusted does not necessarily have to be
set to the same baud rate as the PC, as the adjustment pro-
cedure is accomplished as described below:
The adjustment or modification of address and baud rate via
bus is always carried out together with the loading of a
new configuration by means of the configuration software
COMBILOG.EXE. The download is carried out as described in
the online help for the configuration software. The LEDs at the
front indicate which data logger is being newly adjusted at the
moment. If the LED ERR changes from "off" to "flash", a new
program is just being transmitted to the data logger. The values
are taken over as soon as the data transmission via bus has
been successfully completed.
Note: The address “0” is reserved for transmission via
PROFIBUS. This address can therefore not be assigned to a
logger.
Hardware Manual COMBILOG 1022
98