8 modbus protocol, 1 telegram format for the modbus-rtu protocol – Kipp&Zonen COMBILOG Data Logger User Manual

Page 129

background image

11.8

MODBUS protocol

11.8.1

Telegram Format for the MODBUS-RTU Protocol

The request and response telegrams in the RTU-mode used by
the sensor modules start with an idle-interval of at least 3.5
character lengths. The simplest way of attaining this is by wait-
ing for at least 4 character-times after receiving the last charac-
ter of a telegram. The telegrams have no Start-Delimiter and no
End-Delimiter either. The first field after that idle-interval is the
ISM-Address (ADR) followed by the function number (FNR)
and the function parameters or data respectively. At the end
the telegrams contain a check sum (CRC) with a length of 16
bits. The check sum is calculated from the whole telegram
without the CRC itself. The CRC-polynomial is: u

15

+ u

13

+ 1.

The start value is hex FFFF.

request telegram

idle interval ADR

FNR

function parameters / data CRC

> 3,5 CT

1 byte 1 byte n byte

2 byte

response telegram

idle interval ADR

FNR

function parameters / data CRC

> 3,5 CT

1 byte 1 byte n byte

2 byte

Hardware Manual COMBILOG 1022