11.11 Modem Connection
In case of using a telephone or GSM modem with the
COMBILOG the modem must at first be initialized by means of
a terminal program. Set the interface settings of the terminal
program to 19200 bps, no parity, and enter the following AT
commands. Refer to your modem manual for a detailed de-
scription of the commands, because some commands may dif-
fer depending on the modem type.
Load default settings
AT&F
Set baud rate to 19200 bps
device dependent
Set auto answer on
*
ATS0=1
Set DSR on
AT&C0
Ignore DTR
AT&D0
Save configuration
AT&W0
* In case the modem is connected to the RS232 port of the
COMBILOG, the data logger will response the incoming call
after 4 rings automatically. Note, that the ring will not be recog-
nised at the RS485 port.
Set the RS232 interface of the COMBILOG to 19200 bps, no par-
ity.
Prepare a cable between modem and COMBILOG as shown:
COMBILOG 1022
MODEM
25-pin
9-pin
TX
2
3
RxD
RX
3
2
TxD
GND
7
5
GND
4
7
RTS
5
8
CTS
6
6
DSR
20
4
DTR
Hardware Manual COMBILOG 1022