2 instruction set in modbus-rtu protocol – Kipp&Zonen COMBILOG Data Logger User Manual
Page 130
11.8.2
Instruction Set in MODBUS-RTU Protocol
With the MODBUS-protocol the data are read and written via
register accesses. The following register accesses are defined
for the communication with the sensor modules:
Function number
Function
03 hex
Read Holding Register (Read/Write-Register)
04 hex
Read Input Register (Read-Only-Register)
06 hex
Pre-set Single Register
08 hex
Diagnostic
10 hex
Pre-set Multiple Register
Table 11.15 MODBUS commands
Read Holding Register
Description:
By this command input/output registers (read/write registers)
can be read.
request telegram
ADR
FNR
REGSTA
REGNUM
CRC
03
MSB
LSB
MSB
LSB
MSB LSB
response telegram
ADR
FNR
BYTNUM
D0 D1
03
…
Dn CRC
MSB LSB
ADR ............ module address (hex 00..7F)
FNR ............ function number (hex 03)
REGSTA ..... address of the first register to be read
REGNUM .... number of registers to be read
Hardware Manual COMBILOG 1022