Note: These specifications refer to bus cables with a conductor
cross section of 0.22 mm² and a permissible signal attenuation
of max. 6 dB referred to the overall length. According to previ-
ous experience the line length can be twice as long if a two-
wire circuit with a conductor cross section of at least 0.5 mm² is
used.

10.4

Bus Cable

For setting up a bus topology a shielded twisted pair with at
least two leads and the following electric characteristic values
should be used:

characteristic impedance

: 100 ... 130

at f > 100 kHz

operating capacity

: max. 60 pF/m

conductor cross section

: min. 0.22 mm² (AWG 24)

attenuation

: max. 6dB referred to the

overall length

Hardware Manual COMBILOG 1022