Kipp&Zonen COMBILOG Data Logger User Manual

Page 44

background image

If the temperature is measured by external cold junction com-
pensation, a second thermocouple of the same type is re-
quired, which is connected in series with the first one. The po-
larity is selected so that the thermoelectric voltages subtract
each other. The second thermocouple is set to a fixed refer-
ence temperature

ϑ

r

(mostly

ϑ

r

= 0°C). The data logger then

calculates the temperature at the measuring position by means
of the linearisation curve as

ϑ

x

= Lin(U

x

+Lin

-1

ϑ

r

). The data log-

ger will be informed about the reference temperature

ϑ

r

via the

configuration software (“cold junction temperature”).

Hardware Manual COMBILOG 1022

44