beautypg.com

5 bus plug – Kipp&Zonen COMBILOG Data Logger User Manual

Page 92

background image

10.5

Bus Plug

For installing the bus cable and the bus interface, 9-channel
D-sub miniature plugs and sockets are used. The pin assign-
ment for the RS485 connection according to PROFIBUS/MOD-
BUS specification is given in table 10.2.

plug

Pin

RS485-

notation

meaning

Profibus

meaning

Modbus

1

5

6

9

DB 9

1

Shield,

protective

Ground

2

RP, Reserved for

Power

VP, positive 5...24 V

D.C. Power Supply

3

RxD/TxD-P, Receive /

Transmit Data-P

PMC, Port Mode Con-

trol

4

CNTR-P, Control-P

5

B / B´

DGND, Data Ground

B/B´, transceiver ter-

minal 1, V1 voltage

( V1 > V0 für binary 1

[OFF state] )

6

VP, Voltage Plus

7

RP, Reserved for

Power

8

C / C´

RxD/TxD-P, Receive /

Transmit Data-N

C/C´, signal and power

supply common

9

A / A´

CNTR-N, Control-N

A/A´ transceiver termin-

al 0, V0 voltage

( V0 > V1 for binary 0

[ON state] )

Table 10.2 Pin assignment D-sub miniature plug according to PROFIBUS /

MODBUS

Hardware Manual COMBILOG 1022