5 digital inputs/outputs (6 per module), 6 interfaces – Kipp&Zonen COMBILOG Data Logger User Manual
Page 150
Accuracy:
0.05 %, (dependent on range)
Resolution:
0.003 .. 0.03 %,
(dependent on range)
Linearity:
0.01 %
Temperature drift:
25 ppm/K
5 ppm/K with additional (ext.) drift
correction
13.5
Digital Inputs/Outputs (6 per Module)
as input:
Function:
status, frequency, counter,
8-bit Graycode receiver
Input voltage:
max. +30 VDC
Input current:
max. 1.5 mA
Input frequency:
max. 4000 Hz
Switching threshold (low): > 3.5 VDC
Switching threshold (high): < 1.0 VDC
Counter width:
16 bit
as output:
Function:
host-out, process-out
Output voltage:
max. 30 VDC
Output current:
max. 100 mA
Type of output:
open collector
13.6
Interfaces
Base:
RS 485, RS 232, Ethernet, USB
RS232 and RS485 galv. isolated
from processor core, no isolation
between channels
Data format:
8E1 / 8N1 / 8O1
Protocol:
ASCII, PROFIBUS, MODBUS
Hardware Manual COMBILOG 1022