3 data format – Kipp&Zonen COMBILOG Data Logger User Manual

Page 101

background image

11.3

Data Format

The data logger COMBILOG 1022 supports following data
formats:

For-

mat

Start

-

bit

Data

-

bit

Parity-

bit

Stop-

bit

Charac

ter

length

ASCII /

Modbus

Profibus

8N1

1

8

N

1

10

X

8E1

1

8

E

1

11

X

X

8O1

1

8

O

1

11

X

8N2

1

8

N

2

11

X

8E2

1

8

E

2

12

X

8O2

1

8

O

2

12

X

Table 11.1 Supported data transfer formats

The data format 8E1 with even parity (E=even) corresponds to
the PROFIBUS-definitions according to DIN 19245, part 1, and
is supported by the data logger both in the PROFIBUS-protocol
and in the ASCII- and MODBUS-protocol. This data format
should therefore generally be selected for the transmission.

For modem connections, which in most cases can be carried
out without a parity-bit, the second data format is available.
This data format is only supported by the ASCII-protocol and
the MODBUS-protocol.

The data format is defined via configuration software
COMBILOG.EXE. If there are no other specifications, the de-
fault adjustment is ”no parity”.

Hardware Manual COMBILOG 1022

101